Products Product detail

KLST-B Standard On-off Electric Actuator

KLST-B Standard On-off Electric Actuator for standard on/off valve automation, with catalog examples KLST-02B, KLST-05B, KLST-10B, KLST-20B, KLST-40B, KLST-60B.

Kailing KLST-B Standard On-off Electric Actuator
PRODUCT INFORMATION

KLST-B is the standard on/off electric actuator structure for open-close rotary valve automation. Use it when you need simple fully open and fully closed control for ball valves, butterfly valves and ventilation valves. Catalog models KLST-02B, KLST-05B, KLST-10B, KLST-20B, KLST-40B and KLST-60B cover output torque from 6 N.m to 6000 N.m, action times of 7 s to 150 s for 0-90 degrees, and DC24V, AC24V, AC110V, AC220V or AC380V power options. Selection should follow the catalog principle that 60%-80% of rated actuator torque covers the valve working torque.

Ordering Code Product configuration
KLST-02-B-AC24V
KLST / KLSTZ / KLSTA Series
  • KLST: normal electric actuator
  • KLSTZ: explosion-proof type
  • KLSTA: waterproof type
02 / 05 / 10 / 20 / 40 / 60 / 100 / 200 / 400 Size
  • Choose by valve torque, DN size and service conditions
B Structure
  • B: Standard on/off
DC24V / AC24V / AC110V / AC220V / AC380V Voltage
  • Confirm actual power supply and control cabinet design

Selection use

Review KLST-B Standard On-off Electric Actuator or related examples such as KLST-02B, KLST-05B, KLST-10B, KLST-20B, KLST-40B, KLST-60B.

Torque selection

The catalog warns that valve type, manufacturer and service environment affect actual torque. Use 60%-80% of actuator rated torque as the valve working-torque reference and confirm with Kailing before final selection.

RFQ confirmation points

For a quotation, provide valve type, DN size, working torque, voltage, open close control, environment, quantity. Include valve drawings or an existing actuator nameplate when replacing a unit.

Technical Specifications Published data
ParameterValue
Actuator familyKLST normal electric actuator, KLSTZ explosion-proof type, KLSTA waterproof type
Size codes02, 05, 10, 20, 40, 60, 100, 200 and 400; selection table also lists KLST-600
Voltage optionsDC24V, AC24V, AC110V, AC220V and AC380V
Torque range in selection table6N.m to 6000N.m by model
Action time range in selection table7s to 150s for 0-90 degrees by model
Selection principleChoose actuator rated output torque so 60%-80% of rated torque covers the valve working torque
Selection noteProduct guide data is a selection reference; confirm actual valve torque, service environment, wiring and current drawing before final quotation
StructureB: standard on/off
Best fitSimple open-close control for ball valves, butterfly valves and ventilation valves
Technical Specifications Published tables

KLST-B Standard On-off Electric Actuator sizing reference

ModelOutput torqueAction time 0-90 degreesPowerValve sizing reference
KLST-026N.m7sAC110/AC220 50/60Hz or DC24Vhard-seal butterfly DN25; soft-seal butterfly up to DN20
KLST-0515/30/50N.m10/20/30sAC110V, AC220V, AC380V, 50/60Hz, DC24Vsoft-seal butterfly up to DN65; ball valve up to DN40; ventilation butterfly DN50-DN80
KLST-1050/60/100N.m13/15/20/30sAC110V, AC220V, AC380V, 50/60Hz, DC24Vhard-seal butterfly DN40-DN65; soft-seal butterfly DN80-DN125; ball valve DN40-DN50
KLST-2080/100/150/200N.m9/15/20/30/60sAC110V, AC220V, AC380V, 50/60Hz, DC24Vhard-seal butterfly DN80-DN125; soft-seal butterfly DN150-DN200; ball valve DN65-DN80
KLST-40/60150/250/400/600N.m9/15/20/30/60sAC110V, AC220V, AC380V, 50/60Hz, DC24Vhard-seal butterfly DN150-DN200; soft-seal butterfly DN250; ball valve DN100-DN125
KLST-100800/1000N.m30/50sConfirm by modelhard-seal butterfly DN250; soft-seal butterfly DN300-DN350; ball valve DN150-DN200
KLST-2002000N.m100sConfirm by modelhard-seal butterfly DN300-DN400; soft-seal butterfly DN400-DN500; ball valve DN250-DN300
KLST-4004000N.m100sConfirm by modelhard-seal butterfly DN400-DN500; soft-seal butterfly DN500-DN600; ball valve DN300-DN400
KLST-6006000N.m150sConfirm by modelprinted soft-seal butterfly range requires confirmation; ball valve DN400-DN500

DN ranges are catalog selection references only. Actual actuator selection must be based on valve working torque and service environment.

KLST-B Standard On-off Electric Actuator technical reference

StructureExamplesReferenceProduct guide pages
Standard on/offKLST-02B, KLST-05B, KLST-10B, KLST-20B, KLST-40B, KLST-60BOrdering-code section lists B as the standard on/off structure, and page 95 provides torque, action-time, voltage and valve-size selection data.95, 96, 97, 98, 99, 100

Frequently Asked Questions

  • FAQ Which source supports KLST-B Standard On-off Electric Actuator?
    This product detail is based on Kailing catalog page 95, 96, 97, 98, 99, 100.
  • FAQ Can KLST be selected by DN size only?
    No. DN ranges are references. Final selection should confirm working torque, valve type, medium, pressure, control signal and environment.

Need a quotation?

Send the model, medium, pressure, port size, body material and quantity for review.

Send RFQ →