Resources Buyer guide

AT Series Pneumatic Actuator: How To Confirm And Install Your Valve Actuator After Selection

After selecting a Kailing AT series pneumatic actuator, confirm mounting, action type, air supply, torque, fail-safe direction, accessories and commissioning before installation.

AT series spring return pneumatic actuator mounted for valve automation

AT Series Pneumatic Actuator: How To Confirm And Install Your Valve Actuator After Selection

Choosing the right actuator is only the first step. After you select a Kailing AT series pneumatic actuator, the next decisions determine whether it starts cleanly and keeps working. This guide walks through the checks that matter after model selection: mounting interface, action type, air supply, torque margin, accessories, commissioning and long-term support.

Key takeaways

  • The AT series is a 90-degree rack-and-pinion pneumatic actuator for ball valves, butterfly valves and other quarter-turn valve packages.
  • Confirm the action type before ordering: AT-D is double acting, while AT-S is single acting spring return.
  • Mount with ISO 5211 / DIN 3337 interfaces and use VDI/VDE 3845 NAMUR pads for solenoid valves, limit switches and positioners.
  • Check valve torque, air pressure, temperature range, travel adjustment and accessory interfaces before final installation.

Why post-selection checks matter

Most actuator problems do not come from a wrong model number alone. They come from a missed detail between model selection and installation: an unmatched flange, insufficient air pressure, an overlooked fail-safe requirement, or an accessory that does not fit the actuator pad. This article helps you close those gaps.

What is a pneumatic actuator?

A pneumatic actuator converts compressed air into rotary motion. The AT series uses a rack-and-pinion mechanism to deliver 90 degrees of rotation with plus or minus 5 percent accuracy. That makes it suitable for quarter-turn valves where open and close positions must be repeatable.

Common applications include:

  • Ball valve automation
  • Butterfly valve automation
  • Process line isolation
  • Utility and fluid-control packages
  • OEM valve assemblies

Which action should you choose after sizing?

Action Option What it does Best for
Double acting AT-D Air pressure drives both open and close strokes Lines with a reliable air supply and no fail-safe position requirement
Single acting spring return AT-S Air drives one stroke; springs return the actuator to a defined position on air loss Fail-close or fail-open requirements

If your process requires a safe position on air failure, define that position before final ordering. The AT-S spring return actuator supports this, but the valve package, torque and spring configuration must match the application.

What are the key specifications to confirm?

Specification AT series reference
Maximum working pressure 10 bar
Double acting operating pressure 3 bar to 8 bar
Single acting operating pressure 5 bar to 8 bar
Rotation 90 degrees, plus or minus 5 percent
Standard temperature range -20°C to +80°C
Optional temperature ranges -35°C to +80°C or -20°C to +150°C
Service life 1,000,000 cycles
Valve mounting ISO 5211 and DIN 3337
Accessory mounting VDI/VDE 3845 NAMUR
Travel adjustment Two independent mechanisms for plus or minus 5 degrees

Torque should always be checked against the actual valve, medium, pressure, temperature and safety factor. Catalog torque tables are references, not a substitute for final sizing.

What should you check before mounting the actuator?

1. Valve interface

Confirm that the valve stem dimensions and ISO 5211 flange match the selected actuator size. Older valve bodies may use DIN 3337. If the interface differs, use a mounting bracket and coupling designed for the actual valve.

2. Air supply

Check operating pressure against the action type. Double acting models operate from 3 to 8 bar. Spring return models require 5 to 8 bar. Confirm air quality and drainage so internal seals and springs are not affected by moisture or contamination.

3. Torque margin

Use the valve manufacturer's breakaway torque, not just nominal torque. Add the required safety factor for media, temperature and wear. If the valve operates against dirt, slurry, scale or high differential pressure, increase the margin and confirm the actuator size again.

4. Fail-safe direction

For spring return actuators, define whether the valve should go to open, closed or another safe position when air is lost. Confirm this with the process engineer and record it on the datasheet before shipping.

5. Accessories

The top and side interfaces follow VDI/VDE 3845 NAMUR. That allows direct mounting of:

  • Solenoid valves
  • Limit switch boxes
  • Positioners
  • Other automation accessories

Confirm electrical ratings, enclosure protection, explosion-proof requirements and signal type for each accessory.

How should you commission the actuator?

  1. Check that the valve is in the correct manual position before connecting the actuator.
  2. Confirm the coupling is aligned and secured.
  3. Verify travel stops against the valve's open and close positions.
  4. Apply air gradually and check for leakage.
  5. Cycle the valve and confirm stroke direction.
  6. Adjust travel if the valve requires plus or minus 5 degrees of correction.
  7. Test solenoid signals, limit switches and positioner feedback.
  8. Record final settings for maintenance and future replacement.

What materials are used?

The AT series uses an extruded aluminium alloy cylinder, die-cast aluminium pistons and end caps. Standard O-rings are NBR, with FKM or silicone rubber options depending on temperature and media. Springs are high alloy spring steel with epoxy coating.

These material choices suit general pneumatic automation and many valve-control applications. For aggressive media or unusual temperatures, confirm seal compatibility before ordering.

Frequently asked questions

What is the difference between AT-D and AT-S?

AT-D is double acting. It uses air pressure for both open and close strokes. AT-S is single acting spring return. It uses air for one stroke and springs for the return stroke, allowing a defined fail position on air loss.

Can the AT actuator mount solenoid valves directly?

Yes. The side connection follows VDI/VDE 3845 NAMUR and supports direct solenoid valve mounting without an adapter plate, provided the solenoid valve uses the matching interface.

Is the torque table enough to select an actuator?

No. The torque table is only a reference. Final sizing should include valve torque, safety factor, medium, pressure, temperature and service conditions.

Can I use the AT series for valves other than ball valves?

The series is intended for 90-degree rotary valves such as ball valves, butterfly valves and other quarter-turn valve packages. Confirm the valve torque and operating conditions before final selection.

What information should I provide after selecting a model?

Provide valve type, valve torque, actuator action, air pressure, temperature range, mounting flange, accessories, quantity and preferred color or coating. This allows the supplier to confirm compatibility and final configuration.

Get installation and configuration support

If you have already selected an AT series pneumatic actuator, send your valve datasheet, torque requirement, air supply conditions and accessory list. Kailing can help confirm the interface, fail-safe configuration and commissioning details before installation.

Need a quotation?

Send the page link, quantity, drawings and working conditions to Kailing for review.

Send RFQ →